AAON PREHEAT-X Series Module Controller

Produkspesifikasies
- Model: PREHEAT-X Module
- Controllers: VCCX-IP, VCCX2, VCB-X, VCM-X E-BUS
- Sensors: Air Temperature Sensor, Outside Air Sensor
- Cable Assembly: E-BUS Cable Assembly
- Power & Comm Cable Lengths: 1.5 Ft, 3 Ft, 10 Ft, 25 Ft, 50 Ft, 75 Ft, 100 Ft, 150 Ft, 250 Ft, and 1000 Foot Spool
Produkgebruiksinstruksies
Algemene inligting
The PREHEAT-X Module is designed to regulate temperature in HVAC systems. It works in conjunction with various controllers and sensors to maintain desired temperatures.
Insette en Uitsette
The module supports analog and binary inputs, analog outputs, and relays for precise control over the HVAC system. Refer to the user manual for detailed configuration options.
Volgorde van bedrywighede
The module offers different operation modes to suit various heating requirements. Users can select the appropriate mode based on their needs for efficient temperature control.
Probleemoplossing
In case of issues, refer to the LED diagnostics section in the manual to identify problems. The module also features alarms toalert users of any malfunctions that may occur during operation.
| VOORVERHIT-X HERSIENINGSLOG | |
| HERSIENING EN DATUM | VERANDER |
|
Ds E, 16 April 2021 |
Opgedateerde onderdeelnommers, alarms en alarmgeskiedenis, en etikette. Figuur-/Tabel-inhoudsbladsye en Fahrenheit/Celsius temperatuuromskakeling bygevoeg. Kosmetiese foute reggestel. |
| Eerw. F, 2 Februarie 2024 | opgedateerde skerms, opgedateerde onderdeletabel, verskeie kosmetiese opdaterings |
| VERWYSING VAN ONDERDELE VIR VOORVERHITING-X | |
| DEELBESKRYWING | DEELNOMMER |
| VOORVERHIT-X Module | ASM01688 |
| VCCX-IP-beheerder | ASM07424 |
| VCCX2 beheerder | ASM01698 |
| VCB-X-beheerder | ASM01862 |
| VCM-X E-BUS-beheerder | V07151 |
| Lugtemperatuursensor | G051240 (6 duim), G051250 (12 duim) |
| Buitelugsensor | G042230 |
| E-BUS Kabelsamestelling E-BUS Krag & Kommunikasie 1.5 Vt, 3 Vt, 10 Vt, 25 Vt, 50 Vt, 75 Vt, 100 Vt, 150 Vt, 250 Vt, en 1000 Vt Spoel | G029440 (1.5 vt), G012870 (3 vt), G029460 (10 vt), G045270 (25 vt), G029510 (50 vt), G029530 (75 vt), G029450 (100 vt), G029470 (150 vt), V36590 (250 vt), G018870 (SPOOL) |
Alle handleidings is ook beskikbaar vir aflaai vanaf www.aaon.com/controlsmanuals.
- AAON
- 2425 South Yukon Ave. Tulsa, OK 74107-2728
- www.aaon.com
- Fabriek tegniese ondersteuning telefoon: 918-382-6450
- AAON Kontroles Ondersteuning: 866-918-1100
- Dit is die bedoeling van AAON om akkurate en huidige produkinligting te verskaf. In die belang van produkverbetering behou AAON egter die reg voor om pryse, spesifikasies en/of ontwerp van sy produk sonder kennisgewing, verpligting of aanspreeklikheid te verander.
- AAON P/N: G086640, Rev. F
- © February 2024 AAON Inc. All rights reserved throughout the world.
- AAON® is a registered trademark of AAON, Inc., Tulsa, OK. AAON assumes no responsibility for errors or omissions in this document.
- Hierdie dokument is onderhewig aan verandering sonder kennisgewing.
VERBYVIEW
- Die PREHEAT-X is ontwerp om vaste s te beheertagVoorverhitting en opsionele modulerende voorverhitting om 'n verlangde voorverhittingstemperatuur-instelpunt vir uitgaande lug te handhaaf. Sien Figuur 1, hierdie bladsy vir afmetings. Sien Figuur 2 en 3, bladsye 7 en 8 vir bedradingsbesonderhede.
Kenmerke
Die PREHEAT-X het die volgende kenmerke:
- Kan as 'n losstaande module bedryf word of met die VCCX2 of ander AAON-eenheidbeheerders kommunikeer.
- Monitor die voorverwarmer se uittredelugtemperatuur en die uittredelug-terugstelsein en beheer om die ingestelde punt te handhaaf
- Bevat 'n 2 x 8 LCD-karakterskerm en vier knoppies wat statusvertoning en instelpuntveranderinge moontlik maak
LET WEL: Die PREHEAT-X bevat geen onderdele wat deur die gebruiker onderhou kan word nie. Kontak gekwalifiseerde tegniese personeel indien u PREHEAT-X nie korrek werk nie.

BEDRADING
Belangrike bedradingsoorwegings
Die modules moet gekoppel word aan 'n 18-30 VAC-kragbron van die korrekte grootte vir die berekende VA-lasvereistes. Alle transformatorgroottes moet gebaseer wees op die VA-graderings wat in Tabel 1, hierdie bladsy, gelys word.
|
Beheer Toestel |
Voltage |
VA-lading |
Bedryfstemperatuur |
Humidity (Non- Condensing) |
|
PREHEAT-X |
18-30 VAC | 18 | -22°F tot 158°F*
-30ºC to 70ºC* |
0-95% RH |
|
Insette |
Resistive Inputs require 10KΩ
Type III Thermistor |
|||
| 24 VAC Inputs provide 4.7KΩ
Laai |
||||
| Uitsette | Aflos uitsette: 1 amp maksimum per uitset. | |||
Table 1: PREHEAT-X Electrical and Environmental Requirements
LET WEL: As die temperatuur by die PREHEAT-X onder -22ºF (-30ºC) is, kan die skerm se verversingstempo minder responsief wees.
WAARSKUWING: Wanneer 'n enkele transformator gebruik word om meer as een beheerder of uitbreidingsmodule aan te dryf, moet die korrekte polariteit altyd tussen die borde gehandhaaf word. Versuim om die korrekte polariteit na te kom, sal lei tot skade aan die AAON-eenheidbeheerder, PREHEAT-X en enige geassosieerde module.
Lees asseblief die volgende inligting sorgvuldig deur en pas dit toe wanneer u die AAON-eenheidbeheerder, PREHEAT-X en enige geassosieerde module bedraad.
-
Alle bedrading moet in ooreenstemming wees met plaaslike en nasionale elektriese kodes en spesifikasies.
-
Alle 24 VAC-bedrading moet so gekoppel wees dat alle aarddrade gemeenskaplik bly. Versuim om hierdie prosedure te volg, kan skade aan die beheerder en gekoppelde toestelle veroorsaak.
-
Minimum draadgrootte vir 24 VAC-bedrading moet 18-gaas wees.
- Die minimum draadgrootte vir alle sensors moet 24-gauge wees. Sommige sensors benodig tweegeleierdraad en ander drie- of viergeleierdraad.
- Die minimum draadgrootte vir 24 VAC termostaatbedrading moet 22-gauge wees.
- Maak seker dat alle bedradingsverbindings behoorlik in die terminaalblokke geplaas en vasgedraai is. Moenie toelaat dat draaddrade uitsteek en aangrensende terminale raak nie, wat moontlik 'n kortsluiting kan veroorsaak.
- Wanneer kommunikasiebedrading gebruik gaan word om AAON-eenheidbeheerders met mekaar te verbind of om aan ander kommunikasietoestelle te koppel, moet alle bedrading plenum-gegradeer wees, minimum 18-gauge, twee-geleier, gedraaide paar met afskerming. AAON kan kommunikasiedraad verskaf wat aan hierdie spesifikasie voldoen en kleurgekodeer is vir die netwerk of plaaslike lus. Raadpleeg asseblief u AAON-verspreider vir inligting. Indien verkies, kan Belden #82760 of ekwivalente draad ook gebruik word.
- Voordat u krag aan die AAON-eenheidbeheerder, PREHEAT-X en enige geassosieerde modules toepas, maak seker dat u alle bedradingsverbindings en terminasies deeglik nagaan.
Aan die gang
Wanneer die beheerder en modules vir die eerste keer aangeskakel word, behoort die POWER-LED aan te brand en aanhoudend aan te bly. Indien dit nie aanbrand nie, maak seker dat jy 24 VAC aan die beheerder gekoppel het, dat die bedradingsverbindings styf is, en dat hulle vir die korrekte polariteit bedraad is. Die 24 VAC-krag moet so gekoppel word dat alle aarddrade gemeenskaplik bly. Indien die POWER-LED nie aanbrand nadat al hierdie kontroles gedoen is nie, kontak asseblief AAON Controls-ondersteuning vir hulp.
Insette bedrading
Insette
The PREHEAT-X works as a stand-alone module or comm-unicating with the VCCX2 or other AAON unit controllers. For connection to the PREHEAT-X use an E-BUS Cable connecting to the appropriate E-BUS ports. The Reset Input and Heat Enable are only used in Stand-Alone Mode. See Figure 2, this page for the Inputs Wiring Diagram.

Uitsette Bedrading
Uitsette
Die PREHEAT-X werk as 'n alleenstaande module of kommunikeer met die VCCX2 of ander AAON-eenheidbeheerders. Vir verbinding met die PREHEAT-X, gebruik 'n E-BUS-kabel wat aan die toepaslike E-BUS-poorte gekoppel word. Sien Figuur 3, hierdie bladsy vir die uitsetbedrading.

INSETTE EN UITSETTE
Analoog en binêre insette, analoog uitsette en relais
| Analoge insette | |
| 1 | Uitgaande lugtemperatuur 1 (LAT1) |
| 2 | Uitgaande lugtemperatuur 2 (LAT2) |
| 3 | Inkomende lugtemperatuursensor |
| 4 | Herstel In (0-10 VDC) |
| Binêre insette | |
| 1 | Hitte aktiveer |
| 2 | Noodafskakeling |
| 3 | Toekomstige gebruik |
| Analoog uitsette | |
| 1 | 0-10 VDC Mod SCR |
| 2 | PWM SSR |
| Relais | |
| 1 | Alarm |
| 2 | Hitte 1 |
| 3 | Hitte 2 |
| 4 | Hitte 3 |
| 5 | Hitte 4 |
| 6 | Hitte 5 |
| 7 | Hitte 6 |
Tabel 2: VOORVERHIT-X Insette en Uitsette
I/O Kaart
Sien Tabel 2, hierdie bladsy, om die insette en uitsette te verwys wat op die PREHEAT-X beskikbaar is.
Analoge insette
- Uitgaande lugtemperatuur 1 (LAT1)
Wanneer dit geaktiveer is, sal die PREHEAT-X beheer word na 'n uitgaande lugtemperatuur (LAT) instelpunt. Die PREHEAT-X kan gekonfigureer word om slegs LAT1 vir hierdie doel te gebruik. Tipies word die gemiddelde van LAT1 en LAT2 gebruik. - Uitgaande lugtemperatuur 2 (LAT2)
Wanneer dit geaktiveer is, sal die PREHEAT-X beheer word na 'n uitgaande lugtemperatuurinstelpunt. Dit kan gekonfigureer word om slegs LAT2 vir hierdie doel te gebruik. Tipies word die gemiddelde van LAT1 en LAT2 gebruik. - Invoer van lugtemperatuur
Wanneer die intreelugtemperatuur onder die intreelugtemperatuurinstelpunt daal, sal voorverhitting geaktiveer word.
LET WEL: Vir AI1 tot AI3 moet alle temperatuursensors Termistor Tipe III Temperatuursensors wees, wat 77.0ºF @ 10K ohm weerstand bied.
Herstel-invoer (0-10 VDC)
Wanneer die PREHEAT-X as 'n losstaande module gebruik word, kan die Uitgaande Lugtemperatuurinstelpunt herstel word deur 'n 0-10 VDC-sein aan die RST IN lae volume te verskaf.tage-terminaalblok. Hierdie herstelsein is opsioneel en hoef slegs gebruik te word as u die uitlaatlugtemperatuur moet herstel.
Binêre insette
- Hitte-aktiveerkontak (HEAT EN)
Hierdie invoer word slegs benodig wanneer die PREHEAT-X as 'n alleenstaande module gebruik word; dit word nie benodig wanneer met 'n AAON-eenheidbeheerder gekommunikeer word nie. Die Hitte-aktiveer-inset word geaktiveer deur 'n 24 VAC-sein wat vanaf 'n gebou-outomatiseringstelsel voorsien word om die PREHEAT-X te aktiveer. Die module sal nie werk sonder dat 24 VAC op hierdie invoerterminaal toegepas word wanneer dit as 'n alleenstaande module gebruik word nie. Wanneer die Hitte-aktiveer-sein verlore gaan of afgeskakel word, sal alle ...tages deaktiveer onmiddellik. - Noodafskakeling-invoer
Hierdie nat kontak (24 VAC) inset word gebruik om die afskakeling van die HVAC-eenheid te begin wanneer 'n NC-rookmelder (deur ander), brandmelder (deur ander) of ander afskakeltoestand (deur ander) voorkom en die kontak oopgemaak word. Die PREHEAT-X bly aktief en kan alarmrelais begin.
Analoog uitsette
- 0-10 VDC Modulerende SCR
Afhangende van die tipe hitte wat gebruik word, sal hierdie uitset 'n 0-10 VDC-uitsetsein lewer vir die beheer van die modulerende SCR-hitte. - Pulswydte-modulerende SSR
Afhangende van die tipe hitte wat gebruik word, sal hierdie uitset 'n 12 V PWM-uitsetsein lewer vir die beheer van die modulerende SSR-hitte.
Aflosuitsette
- Relais #1 – Alarm
Hierdie relais stuur 'n sein wanneer 'n alarm geaktiveer is. - Relais #2 – 7
Hierdie relais is Vaste Stage Hitte-uitsette.
OPVolging van bedrywighede
Bedryfsmodusse
Die PREHEAT-X kan as 'n alleenstaande module gebruik word of met 'n AAON-eenheidbeheerder kommunikeer deur 'n modulêre kabel te gebruik.
Losstaande modus
Wanneer dit in alleenstaande modus gebruik word, sal die PREHEAT-X SCR- of SSR-verhitting moduleer en ...tagenige bykomende vaste stagom die Uitgaande Lugtemperatuurinstelpunt wat op die PREHEAT-X LCD-skerm gekonfigureer is, te handhaaf. Die PREHEAT-X word geaktiveer deur 'n 24 VAC-sein na die HEAT EN-inset.
Kommunikasiemodus
- Wanneer die PREHEAT-X gekoppel is en met 'n AAON-eenheidbeheerder kommunikeer via 'n modulêre kabel, sal die nodige inligting tussen die PREHEAT-X en die AAON-eenheidbeheerder oorgedra word om behoorlik in die Verhittingsmodus te werk.
- Indien die kommunikasie tussen die PREHEAT-X en die AAON-eenheidbeheerder onderbreek word, sal beide borde 'n alarm wys en die PREHEAT-X-uitsette sal afskakel. Wanneer kommunikasie herstel is, sal die alarms verdwyn.
- In hierdie konfigurasie word die Uitgaande Lugtemperatuur-instellingspunte en die Voorverhitting-aktiveerpunte ingestel met behulp van die hoof AAON-eenheidbeheerder.
Voorverhit Aktiveer
Losstaande modus
Geaktiveer wanneer die binêre invoer gesluit is en die intreelugtemperatuur onder die ingestelde punt is.
E-BUS Kommunikasiemodus
Word deur 'n E-BUS-opdrag geaktiveer wanneer die intreelugtemperatuur onder die voorverhittingsinstelpunt daal.
BACnet Kommunikasiemodus
Geaktiveer deur BACnet®-opdrag of binêre invoer, wat ook al eerste plaasvind.
Verlatende lugsensor
Die PREHEAT-X kan gekonfigureer word om een van drie sensorkonfigurasies vir beheer te gebruik.
- Slegs Verlatende Lugsensor 1 (LAT1)
- Slegs Verlatende Lugsensor 2 (LAT2)
- Gemiddelde uitgaande lugtemperatuur wat gemiddeld LAT1 en LAT2 is
Uitgaande luginstellingspunt
Alleenstaande
- Die uitgaande lugtemperatuurinstelpunt kan herstel word tussen die LAT-instelpunt en die LAT-instelpuntherstellimiet.
- Die Herstelbron is gebaseer op 'n 0-10 VDC-inset en die reeks kan aangepas word met behulp van die LAT-instelpunt-herstelbron-laag en LAT-instelpunt-herstelbron-hoë instelpunte.
E-BUS and BACnet Communications Mode
- 'n Uitgaande lugtemperatuurinstelpunt sal na die beheerder gestuur word.
- Hierdie waarde word in vlugtige geheue gestoor en sal verlore gaan met herstel.
- Daar is afsonderlike uitlaatlugtemperatuur-instellings, afhangende van of die eenheid in verhittings-, ventilasie- of verkoelingsmodus is.
Modulerende hitte
- Indien gekonfigureer, sal die Modulerende Hitte-uitset as die eerste s gebruik word.tage van hitte.
- Analoog Voltage Uitset kan aangepas word tussen 0-10 VDC soos nodig om die uitgaande luginstelpunt te handhaaf.
- Beheer deur 'n interne PID-lus.
Verhit StagOp
Die volgende voorwaardes moet nagekom word voor die eerste (volgende) stage van hitte kan energiek gemaak word:
- Voorverhitting-aktiveersein/-bevel moet aktief wees.
- Die LAT moet met enige bedrag onder die LAT-instelpunt wees.
- As Mod Heat gekonfigureer is, moet dit op 100% wees vir die S.tage Opwaartse Vertraging.
- Die Minimum Aftyd moet nagekom word.
- Die Stage Opwaartse Vertraging moet nagekom word (vir sekondes stage en hoër).
Verhit Stagaf
Die volgende voorwaardes moet nagekom word voordattage van hitte kan gedeenergiseer word:
- Preheat Enable Signal/Command is deactivated -ORthe LAT must be above the LAT Setpoint by the LAT Deadband.
- Indien Modulerende Verhitting gekonfigureer is, moet dit op 0% wees vir die Stage Afwaartse vertraging.
- Die Minimum Looptyd moet nagekom word.
- Die Stage Stilstandtyd moet nagekom word.
Noodafskakeling
Die Noodafsluiting-inset moet altyd gebruik en bedraad word as 'n 24 VAC normaalweg geslote kontak. Indien 'n Noodafsluiting plaasvind en daardie kontak oopmaak:
- Alle uitsette sal onmiddellik gedeaktiveer word.
- 'n Alarm sal gegenereer word.
Alarm vir hoë uitgaande lugtemperatuur
If the Leaving Air Temperature is above the LAT High Temperature Alarm Limit for more than the Alarm Delay, all heating outputs will be de-energized immediately.
- 'n Alarm sal gegenereer word.
- 'n Handmatige herstel sal vereis word.
Lae uitgaande lugtemperatuur-alarm
Indien die uitgaande lugtemperatuur vir meer as twee minute onder die LAT lae temperatuur-alarmlimiet is, sal die verhitting aan bly, maar 'n alarm sal gegenereer word.
LCD-SKERMS
Navigasie sleutels
LCD-skerm en navigasiesleutels
Die LCD-skerms en knoppies laat jou toe om view status en alarms, en aktiveer kragmodusse. Sien Figuur 4, hierdie bladsy en verwys na Tabel 3 en 4, hierdie bladsy vir beskrywings.


LCD-SKERMS
Hoofskerms Kaart

Hoofskerms
Refer to the following map when navigating through the LCD Main Screens. The first screen is an initialization screen. To scroll through the rest of the screens, press the <MENU> button.

- Druk
om deur PREHEAT-X-skerms te blaai. - Druk
om na STATUS-skerms te gaan.

- Druk
om deur STATUS-skerms te blaai. - Druk
om na SETPOINTS-skerms te gaan.

- Druk
om deur INSTELPUNTE-skerms te blaai. - Druk
om na ALARMS-skerms te gaan.

- Druk
om deur ALARMS-skerms te blaai. - Druk
om na KONFIG-skerms te gaan.

- Druk
om deur KONFIG-skerms te blaai. - Druk
om na COMM CONFIG-skerms te gaan.

- Druk
om deur COMM CONFIG-skerms te blaai.
Status skerms
Verwys na die volgende kaart wanneer u deur die statusskerms navigeer. Druk vanaf die STATUS-skerm op om deur die skerms te blaai.


Setpoint Screens
Verwys na die volgende kaart wanneer u deur die Instelpuntskerms navigeer. Druk vanaf die INSTELPUNTE-skerm op om deur die skerms te blaai en stelpunte te verander. Gebruik die en pyltjie sleutels om jou keuses te verander. Druk dan om die nuwe stelpunt te stoor.
LET WEL: When the PREHEAT-X-EXT is operating in Communications Mode, these setpoint screens will not appear on the LCD display because they are controlled by the main controller.

UITLEGLUGTEMPERATUURINSTELLINGSPUNT
Sal slegs in Alleenstaande Modus vertoon. Dit is die teikentemperatuur terwyl die verhitting geaktiveer is. As jy die herstelsein gebruik, is dit die instelpunt wat dit teen nul volt sal bereken.
| Minimum | Verstek | Maksimum |
| 0ºF | 70ºF | 90ºF |
| -17.7ºC | 21ºC | 32ºC |

HERSTEL LIMIETINSTELPUNT
Sal slegs in Alleenstaande Modus vertoon en gebruik word. Indien Afstandsherstel gebruik word, sal dit die Uitlaatlug-instelpunt wees wanneer die Herstelvolumetage Invoer is teen 10 VDC.
| Minimum | Verstek | Maksimum |
| 0ºF | 70ºF | 120ºF |
| -17.7ºC | 21ºC | 48.8ºC |

INGANGSLUG INSTELPUNT
Dit is die temperatuur waar Voorverhitting geaktiveer is. Die Intreelug Aktiveringsinstelpunt word deur die LCD-skerm in Alleenstaande Modus ingestel en deur die AAON-eenheidbeheerder in Kommunikasiemodus ingestel.
| Minimum | Verstek | Maksimum |
| -40ºF | 55ºF | 90ºF |
| -40ºC | 12.7ºC | 32ºC |

UITLEGLUGSENSOR 1 KALIBRASIEVERSKIL
Indien die sensor verkeerd lees, kan jy hierdie skerm gebruik om 'n verrekeningstemperatuur in te voer om die sensor se temperatuur aan te pas.
| Minimum | Verstek | Maksimum |
| -100ºF | 0ºF | 100ºF |
| -55.5ºC | 0ºC | 55.5ºC |

UITLEGLUGSENSOR 2 KALIBRASIEVERSKIL
Indien die sensor verkeerd lees, kan jy hierdie skerm gebruik om 'n verrekeningstemperatuur in te voer om die sensor se temperatuur aan te pas.
| Minimum | Verstek | Maksimum |
| -100ºF | 0ºF | 100ºF |
| -55.5ºC | 0ºC | 55.5ºC |

INGANGSLUGSENSORKALIBRASIE-VERSKIL
Indien die sensor verkeerd lees, kan jy hierdie skerm gebruik om 'n verrekeningstemperatuur in te voer om die sensor se temperatuur aan te pas.
| Minimum | Verstek | Maksimum |
| -100ºF | 0ºF | 100ºF |
| -55.5ºC | 0ºC | 55.5ºC |
Alarmskerm
- Verwys na die volgende kaart wanneer viewdie ALARMS-skerms. Hierdie skerms sal outomaties vertoon wanneer alarms teenwoordig is. Vir alarmfoutopsporing, sien bladsye 22-23.

Alarms
Die alarms is soos volg:
- NO ALARMS: This will be shown if there are no current alarms.
- E-SHUTDN: If 24 VAC is removed from the Emergency Shutdown Input, this alarm will activate and the controller will turn off all outputs. The alarm will be disabled when voltage het teruggekeer.
- LA1 SENS: The first Leaving Air Temperature sensor has been disconnected, shorted, open, or missing for more than 60 seconds. This alarm will be disabled when the sensor is working again.
- LA2 SENS: The second Leaving Air Temperature sensor has been disconnected, shorted, open, or missing for more than 60 seconds. This alarm will be disabled when the sensor is working again.
- LOW LAT: This indicates a Leaving Air Temperature Cutoff alarm condition which is activated if the Controlling Leaving Air Temperature has dropped below 35ºF for more than two minutes. The alarm will be disabled if after a fixed delay period the Leaving Air Temperature has risen above 35ºF.
- HI LAT: This indicates a Leaving Air Temperature Cutoff alarm condition which is activated if the Controlling Leaving Air Temperature has risen above 120ºF. All outputs will stage af.
- EA SENS: The Entering Air Temperature sensor has been disconnected, open, shorted, or missing for more than 60 seconds. This alarm will be disabled when the sensor is working again.
- COM STAT: Communications have been lost with the main controller for more than 30 seconds. This alarm will disable when communications resume.
Konfigurasie skerms
- Verwys na die volgende kaart wanneer u deur die konfigurasieskerms navigeer. Druk vanaf die KONFIG-skerm op om deur die skerms te blaai en stelpunte te verander. Gebruik die en pyltjie sleutels om jou keuses te verander. Druk om enige veranderinge te stoor.
LCD-SKERMS
Kommunikasiekonfigurasieskerms
- Verwys na die volgende kaart wanneer u deur die Kommunikasiekonfigurasieskerms navigeer. Druk vanaf die COMM CONFIG-skerm om deur die skerms te blaai en stelpunte te verander. Gebruik die en pyltjie sleutels om jou keuses te verander. Druk om enige veranderinge te stoor.

PROBLEEMOPLOSSING
Algemeen
The PREHEAT-X is equipped with LEDs that can be used to verify operation and perform troubleshooting. See Figure 6, this page for the LED locations. The LEDs associated with these inputs and outputs allow you to see what is active without using a voltmeter.
The LEDs and their uses are as follows:
- STATUS LED's
KRAG – Hierdie groen LED sal aanlig om aan te dui dat 24 VAC-krag na die beheerder toegepas is. - Diagnostiese LED's
ALARM – Hierdie rooi LED wat op die PREHEAT-X se deksel bo die LCD-skerm geleë is, sal aanskakel om 'n alarm aan te dui. Die tipe alarm(s) sal op die LCD-skerm vertoon word.
Kommunikasie LED
KOMM – Hierdie geel LED sal aanskakel en flikker wanneer kommunikasie bespeur word.
Relais LED's
RLY 1-6 – Hierdie groen LED's sal aanskakel en bly brand solank die hitte-relais(se) aktief is.
Binêre invoer-LED's
- VERHITTE – Hierdie groen LED sal aanskakel wanneer Verhitting geaktiveer is.
- NOODAFSLUITTING – Hierdie groen LED sal aanlig wanneer die noodafsluitinvoer 24 VAC daarop toegepas word.

Alarms
Foutsporing van alarms
Meganiese mislukking:
- Kontroleer relai-uitsette op die PREHEAT-X vir 24 VAC-uitset.
- Verifieer uitset voltage (VOUT en GND) na SCR of PWM.
- Verifieer dat die uitgaande lugtemperatuursensor(s) aan AI1 en/of AI2 en GND op die PREHEAT-X gekoppel is.
- Verifieer dat die uitlaatlugtemperatuursensor(s) korrek gemonteer is.
- Verwyder AI1 en AI2 en GND bedrading van die PREHEAT-X en koppel die sensor uit (dit kan dui op oop of mislukte bedrading). Verwys na die tabel agter in hierdie gids vir lesings.
Leaving Air Temperature Failure:
- Verifieer dat die uitgaande lugtemperatuursensor(s) aan die AI1 en/of AI2 en GND op die PREHEAT-X gekoppel is.
- Verwyder AI1 en AI2 en GND bedrading van die PREHEAT-X en koppel die sensor uit (dit kan dui op oop of mislukte bedrading). Verwys na die tabel agter in hierdie gids vir lesings.
Communications Loss:
- Kontroleer COMM LED op PREHEAT-X.
- Verifieer 24 VAC-krag na alle gekoppelde beheerders.
- Verifieer die verbinding tussen die PREHEAT-X en geassosieerde beheerders.
- In Kommunikasiemodus (gekoppel met 'n modulêre kabel), verifieer die PREHEAT-X-konfigurasie op die beheerder.
Montering van die uitgaande lugtemperatuursensor
- Die uitgaande lugtemperatuursensor (LAT) moet in die PREHEAT-X-boks se uitvoerligging geleë wees.
- Plaas die sensor in die middel van die breedste deel van die PREHEAT-X-bokswand. Gebruik die meegeleverde sjabloon en 'n 5/16 duim-boor om 'n gat vir die sensor te maak.
- Installeer die pakking oor die sonde en monteer dit stewig aan die bokswand met die meegeleverde plaatmetaalskroewe. Maak seker dat die pakking saamgepers is om 'n lugdigte seël te bied.
Vir die beste akkuraatheid, dien isolasie aan die buitekant van die bokswand, oor die sensor, toe. Dit sal help om te verhoed dat termiese gradiënte die sensor beïnvloed.
WAARSKUWING:
Maak seker dat jou uitlaatlugtemperatuursensor(s) volgens hierdie instruksies gemonteer en bedraad is voordat jy die eenheid toets, anders sal die modulerende klep nie behoorlik beheer nie en kan dit jou toerusting beskadig.

AANHANGSEL A: LAT-SENSOR
Uitgaande lugtemperatuursensor
- Indien u vermoed dat die in- of uitgaande lugtemperatuursensor nie korrek lees nie, maak seker dat die bedradingsterminale styf is en dat enige bedradingslasse behoorlik gekoppel is. U kan die werking van die uitgaande lugtemperatuursensor nagaan deur die weerstand of volume te meet.tage met behulp van 'n digitale multimeter. Stel die meter op GS-volt. Plaas die positiewe sonde op die KI-terminaal en die negatiewe sonde op die GND-terminaal. Lees die GS-volt en vind daardie vol.tage in Tabel 5, hierdie bladsy.
- Lees die temperatuur wat ooreenstem met daardie volumetage and determine if this is close to the actual temperature the sensor is exposed to. If the temperature from the chart is different by more than a few degrees, you probably have a defective or damaged sensor.
- You can also check the sensor resistance to determine correct operation.
Instruksies vir die toets van die termistorsensor
- Om die weerstand te lees, stel die meter op ohm. Ontkoppel die sensorkonnektor van die bord en meet die weerstand oor die ontkoppelde drade. Hierdie weerstand moet ooreenstem met die ooreenstemmende temperatuur van Tabel 5, hierdie bladsy.
Instruksies vir die toets van die termistorsensor
- Gebruik die weerstandskolom om die termistorsensor te kontroleer terwyl dit van die beheerders ontkoppel is (nie aangedryf nie).
- Gebruik die voltage-kolom om sensors na te gaan terwyl dit aan aangedrewe beheerders gekoppel is. Lees volumetage met die meter ingestel op GS-spanning. Plaas die "-" (minus) draad op die GND-terminaal en die "+" (plus) draad op die sensor-insetterminaal wat ondersoek word.
| Temperatuur tot Weerstand/Voltage Grafiek | |||||||
| Temp (°F) | Temp (°C) | Weerstand (Ohm) | Voltage @ Invoer (VDC) | Temp (°F) | Temp (°C) | Weerstand (Ohm) | Voltage @ Invoer (VDC) |
| -10 | -23.3 | 93333 | 2.98 | 72 | 22.2 | 11136 | 1.74 |
| -5 | -20.6 | 80531 | 2.94 | 73 | 22.8 | 10878 | 1.72 |
| 0 | -17.8 | 69822 | 2.89 | 74 | 23.3 | 10625 | 1.70 |
| 5 | -15 | 60552 | 2.83 | 75 | 23.9 | 10398 | 1.68 |
| 10 | -12.2 | 52500 | 2.77 | 76 | 24.4 | 10158 | 1.66 |
| 15 | -9.4 | 45902 | 2.71 | 78 | 25.6 | 9711 | 1.63 |
| 20 | -6.6 | 40147 | 2.64 | 80 | 26.7 | 9302 | 1.59 |
| 25 | -3.9 | 35165 | 2.57 | 82 | 27.8 | 8893 | 1.55 |
| 30 | -1.1 | 30805 | 2.49 | 84 | 28.9 | 8514 | 1.52 |
| 35 | 1.7 | 27140 | 2.41 | 86 | 30 | 8153 | 1.48 |
| 40 | 4.4 | 23874 | 2.33 | 88 | 31.1 | 7805 | 1.45 |
| 45 | 7.2 | 21094 | 2.24 | 90 | 32.2 | 7472 | 1.41 |
| 50 | 10 | 18655 | 2.15 | 95 | 35 | 6716 | 1.33 |
| 52 | 11.1 | 17799 | 2.11 | 100 | 37.8 | 6047 | 1.24 |
| 54 | 12.2 | 16956 | 2.08 | 105 | 40.6 | 5453 | 1.16 |
| 56 | 13.3 | 16164 | 2.04 | 110 | 43.3 | 4923 | 1.09 |
| 58 | 14.4 | 15385 | 2.00 | 115 | 46.1 | 4449 | 1.02 |
| 60 | 15.6 | 14681 | 1.96 | 120 | 48.9 | 4030 | .95 |
| 62 | 16.7 | 14014 | 1.93 | 125 | 51.7 | 3656 | .88 |
| 64 | 17.8 | 13382 | 1.89 | 130 | 54.4 | 3317 | .82 |
| 66 | 18.9 | 12758 | 1.85 | 135 | 57.2 | 3015 | .76 |
| 68 | 20 | 12191 | 1.81 | 140 | 60 | 2743 | .71 |
| 69 | 20.6 | 11906 | 1.79 | 145 | 62.7 | 2502 | .66 |
| 70 | 21.1 | 11652 | 1.78 | 150 | 65.6 | 2288 | .61 |
| 71 | 21.7 | 11379 | 1.76 | ||||
Let wel: As die voltage bo 3.3 VDC is, is die sensor of bedrading "oop". As die volumetagAs e minder as 0.05 VDC is, is die sensor of bedrading kortgesluit.
Tabel 5: 0-3V Temperatuursensor – Voltage & Weerstand vir Tipe III Sensors
AANHANGSEL B: BACnet®
Verbinding met MS/TP-netwerk

| OBJEK | PARAMETER | BESKRYWING | PERKE | |
| KI: 1 | Aktiewe Beheerinstelpunt | Die huidige Aktiewe Beheerinstelpunt | Slegs lees | |
| KI: 2 | Aantal hitte Stagis Aan | Die huidige aantal hittestagis aan | Slegs lees | |
| KI: 3 | Modulerende Uitsetposisie | Die huidige modulerende uitsetposisie | Slegs lees | |
| KI: 4 | Alle alarms Bitfield | Die huidige alarmstatus in 'n bitveld | Lees Alleenlik, sien alarmbits, bladsy 27 | |
| KI: 5 | Invoer van lugtemperatuur | Die huidige intreelugtemperatuur | Slegs lees | |
| KI: 6 | Uitgaande lugtemperatuursensor 1 | Die huidige uitgaande lugsensor 1 temperatuur | Slegs lees | |
| KI: 7 | Uitgaande lugtemperatuursensor 2 | Die huidige uitgaande lugsensor 2 temperatuur | Slegs lees | |
| KI: 8 | Gemiddelde Temperatuur van Uitgaande Lug | Die huidige gemiddelde uitgaande lugtemperatuur | Slegs lees | |
| KI: 9 | Herstel invoerpersentasietage | Die huidige Stelpunt Herstel Invoer Persentasietage | Slegs lees | |
| BI: 1 | Aktiveer invoerwaarde | Die huidige waarde van die Aktiveer Binêre Invoer | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 2 | Afskakeling Invoerwaarde | Die huidige waarde van die Noodafsluiting Binêre Invoer | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 3 | Voorverhitting Aktiveer Status | Die huidige Aktiveerstatus van die beheerder | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 4 | Alarm Relais Status | Die huidige status van die alarmrelais | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 5 | Status van Hitte 1-aflos | Die huidige status van die Heat 1-aflos | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 6 | Status van Hitte 2-aflos | Die huidige status van die Heat 2-aflos | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 7 | Status van Hitte 3-aflos | Die huidige status van die Heat 3-aflos | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 8 | Status van Hitte 4-aflos | Die huidige status van die Heat 4-aflos | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 9 | Status van Hitte 5-aflos | Die huidige status van die Heat 5-aflos | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 10 | Status van Hitte 6-aflos | Die huidige status van die Heat 6-aflos | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 11 | Noodafsluitingsalarm | Die huidige status van die noodafsluitingsalarm | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 12 | Verlatende lugsensor 1 alarm | Die huidige status van die Verlatende Lugsensor 1 Alarm | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 13 | Verlatende lugsensor 2 alarm | Die huidige status van die Verlatende Lugsensor 2 Alarm | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 14 | Lae uitgaande lugtemperatuur-alarm | Die huidige status van die Lae Uitgaande Lugtemperatuur-alarm | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 15 | Alarm vir hoë uitgaande lugtemperatuur | Die huidige status van die hoë uitgaande lugtemperatuur-alarm | Lees Alleen, 0 = Af, 1 = Aan | |
| BI: 16 | Inkomende lugsensoralarm | Die huidige status van die inkomende lugsensor-alarm | Lees Alleen, 0 = Af, 1 = Aan | |
|
AV: 1 |
Afstandsaktiveer |
Aktiveer die voorverhitting vanaf die BACnet®-voorkant |
Lees / Skryf Vlugtig | |
| 0 = Gedeaktiveer, 1 = Geaktiveer | ||||
|
AV: 2 |
Afstandsuitlaatlug-instelpunt |
Beheer van die uitgaande luginstellingspunt vanaf die BACnet®-voorkant |
Lees/skryf vlugtig | |
| 35.0 ºF | 90.0 ºF | |||
|
AV: 3 |
Afstandsinvoerluginstellingspunt |
Voer die Lugaktiveer-instelpunt vanaf die BACnet®-voorkant in |
Lees / Skryf Vlugtig | |
| -40.0 ºF | 90.0 ºF | |||
PREHEAT-X BACnet® Eienskapidentifiseerder
BACNETPropertyIdentifier : AllAlarmGroup1Bits ::= BIT STRING {
- Gereserveer (0),
- SlegteLugVerlaat1 (1),
- SlegteLugVerlaat2 (2),
- Lae Uitgaande Lug (3),
- HoëLuguitlaat (4),
- Gereserveer (5),
- SlegteLugBinnekom (6),
- KommAlarm (7),
- Afskakelalarm (8)
PREHEAT-X Technical Guide G086640 · Rev. F · 240202
- AAON Kontroles Ondersteuning:
- Beheer ondersteuning Webwebwerf:
- AAON Fabriek Tegniese Ondersteuning:
- Telefoon 866-918-1100
- Maandag tot Vrydag, 7:00 tot 5:00 Sentrale Tyd
- LET WEL: Voordat jy tegniese ondersteuning skakel, moet jy asseblief die model en reeksnommer van die eenheid beskikbaar hê.
- ONDERDELE: Vir vervangingsonderdele, kontak asseblief jou plaaslike AAON-verteenwoordiger.
- Is jy 'n AAON-verteenwoordiger?
- Jy kan My AAON besoek om nuwe ondersteuningskaartjies oop te maak, direk met ons ondersteuningspanne te kommunikeer en jou ondersteuningsvordering maklik vanaf een plek na te spoor!
2425 South Yukon Ave • Tulsa, OK • 74107-2728
- Ph: 918-583-2266 • Faks: 918-583-6094
- AAON P/N: G086640, Rev. F
- Gedruk in die VSA • Kopiereg Februarie 2024 • Alle regte voorbehou
Gereelde vrae
Dokumente / Hulpbronne
![]() |
AAON PREHEAT-X Series Module Controller [pdf] Gebruikersgids VCCX-IP Controller, VCCX2 Controller, VCB-X Controller, VCM-X E-BUS Controller, ASM01688, ASM07424, ASM01698, ASM01862, PREHEAT-X Series Module Controller, PREHEAT-X Series, Module Controller, Controller |