BENNING 044104

Benning IT 115 True RMS Installasietoetser Gebruikershandleiding

Model: 044104

1. Inleiding

This manual provides essential instructions for the safe and effective operation of the Benning IT 115 True RMS Installation Tester. This multifunction device is designed for testing electrical installations in accordance with international standards such as DIN VDE 0100-600, IEC 60364-6, DIN VDE 0105-100, and EN 50110. Please read this manual thoroughly before using the instrument.

2. Veiligheidsinligting

WARNING: Electrical shock hazard. Improper use of this instrument can result in injury or death. Always follow safety precautions.

  • Always disconnect all test leads and switch off the instrument before opening the battery/fuse cover.
  • Do not open the battery compartment if hazardous voltage teenwoordig is.
  • Ensure the instrument is in good working condition before use. Do not use if damaged.
  • Observe all local and national safety regulations for electrical work.
  • Only use the provided accessories or approved replacements.
  • Moenie probeer om voltages or currents exceeding the instrument's specified limits.

3. Produk verbyview

The Benning IT 115 is a robust installation tester featuring a backlit graphic display and intuitive controls. It is designed for comprehensive electrical installation testing.

Benning IT 115 True RMS Installation Tester front view

Figuur 3.1: Voorkant view of the Benning IT 115 Installation Tester, showing the display, rotary switch, and control buttons.

Sleutelkomponente sluit in:

  • Graphic Display: Backlit screen for clear readings and connection diagrams.
  • Draaiskakelaar: Selects measurement functions (e.g., R_ISO, R_LOW, Z_L-N/L, Z_L-PE, FI/RCD, SETTINGS).
  • Beheerknoppies: Navigation, TEST, ON/OFF, HELP, ESC.
  • Test Lead Connections: Input terminals for test leads.
  • LED-aanwysers: Green/red LEDs provide quick pass/fail indications.
Benning IT 115 True RMS Installation Tester rear view met batterykompartement

Figuur 3.2: Agter view of the Benning IT 115, showing the battery compartment and safety warnings.

4. Opstelling

4.1. Battery installasie en laai

The Benning IT 115 operates on 6 rechargeable NiMH AA batteries. A charger is included for convenience.

  1. Ensure the instrument is switched off and all test leads are disconnected.
  2. Open the battery compartment cover on the rear of the device (refer to Figure 3.2).
  3. Insert the 6 NiMH AA batteries, observing correct polarity.
  4. Maak die batterykompartement se deksel stewig toe.
  5. Connect the charger to the instrument's charging port and to a suitable power outlet to charge the batteries. The integrated battery charging function will manage the charging process.

NOTE: Do not use non-rechargeable alkaline batteries with the integrated charging function.

4.2. Verbinding van toetsdrade en toebehore

The device comes with a set of accessories for various measurements.

Benning IT 115 accessories including carrying case, test leads, probes, and batteries

Figure 4.1: Included accessories: carrying case, test leads, probes, crocodile clips, and rechargeable batteries.

  • Connect the test cable with the protective contact plug for standard outlet measurements.
  • For other measurements, use the 3-conductor universal cable (1.5 m length) with the provided test probes or crocodile clips as required by the specific test.
  • Ensure all connections are secure before performing any tests.

5. Bedryfsinstruksies

The Benning IT 115 offers a range of measurement functions accessible via the rotary switch and control buttons. The graphic display provides clear readings and a help function with connection diagrams.

5.1. Skakel aan/af

Druk die AAN/AF button to switch the instrument on or off.

5.2. Insulation Resistance Measurement (R_ISO)

Measures insulation resistance between 0.01 MOhm and 1000 MOhm.

  1. Draai die draaiskakelaar na R_ISO.
  2. Select the desired nominal test voltage (50V, 100V, 250V, 500V, 1000V) using the navigation buttons.
  3. Connect the test leads to the circuit under test as indicated by the on-screen help diagram.
  4. Druk die TOETS knoppie om die meting te begin.
  5. The result will be displayed, and the green/red LEDs will indicate pass/fail based on set limits.

5.3. Low-Ohm Resistance Measurement (R_LOW)

Measures low resistance from 0.01 Ohm to 2000 Ohms, typically for protective conductor continuity.

  1. Draai die draaiskakelaar na R_LOW.
  2. Connect the test leads to the protective conductor.
  3. Druk die TOETS button. The instrument uses a 200 mA test current with polarity reversal and a 7 mA test current for continuity.
  4. Observe the displayed resistance value.

5.4. Earth Resistance Measurement (R_E)

Measures earth resistance using the 3-conductor method (requires optional earthing kit 044113).

  1. Draai die draaiskakelaar na R_E.
  2. Connect the optional earthing kit according to the on-screen diagram.
  3. Druk die TOETS knoppie.
  4. The earth resistance value will be displayed.

5.5. Loop and Line Impedance Measurement (Z_L-N/L, Z_L-PE)

Measures loop impedance (0.01 Ohm - 10 kOhm) for fault current path and short-circuit current determination.

  • Line Impedance (Z_L-N/L): Measures impedance between Line and Neutral or Line and Line, including voltage drop and short-circuit current.
  • Loop Impedance (Z_L-PE): Measures impedance between Line and Protective Earth without tripping RCD/FI, including short-circuit current.
  1. Draai die draaiskakelaar na Z_L-N/L or Z_L-PE.
  2. Connect the test leads to the appropriate points in the circuit.
  3. Druk die TOETS knoppie.
  4. The impedance value and calculated short-circuit current will be displayed.

5.6. RCD/FI Test

Tests Residual Current Devices (RCDs) / Fault Current Circuit Breakers (FI) of types AC, A, and F, including standard and delayed (S) types.

  • Tests include automatic test sequences, touch voltage, trip time, and trip current (ramp test).
  • Features an RCD/FI analysis function.
  1. Draai die draaiskakelaar na FI/RCD.
  2. Select the RCD type (AC, A, F) and nominal current using the navigation buttons.
  3. Connect the test leads to the circuit protected by the RCD.
  4. Druk die TOETS button to start the test sequence.
  5. The results (trip time, trip current, touch voltage) sal vertoon word.

5.7. Rotary Field Test

Determines the phase sequence in three-phase systems.

  1. Turn the rotary switch to the rotary field test setting (refer to the device's specific icon).
  2. Connect the test leads to the three phases.
  3. The display will indicate the phase sequence.

5.8. Deeltage en Frekwensiemeting

Maatreëls AC/DC voltage en frekwensie.

  • Voltage reeks: 1 V - 550 V AC/DC (True RMS measurement).
  • Frekwensiereeks: 0 Hz - 20 000 Hz.
  1. The instrument continuously monitors line voltage.
  2. Koppel die toetskabels aan die voltage bron.
  3. Die voltage and frequency will be displayed automatically.

5.9. Help Function

The integrated help function provides connection diagrams and guidance for each measurement. Press the HULP button to access it.

6. Onderhoud

6.1. Skoonmaak

Clean the instrument regularly with a soft, damp lap. Moenie skuur skoonmaakmiddels of oplosmiddels gebruik nie.

6.2. Batteryversorging

Recharge the NiMH batteries when the low battery indicator appears. If the instrument will not be used for an extended period, it is recommended to fully charge the batteries and store the device in a cool, dry place.

6.3. Sekering vervanging

The instrument uses a 0.315 A fuse (part number 757211). If a fuse blows, ensure the instrument is off and disconnected from all circuits before replacing it. Only use fuses of the specified type and rating.

7. Probleemoplossing

  • Instrument does not power on: Check battery charge level. Ensure batteries are correctly inserted.
  • Onakkurate lesings: Ensure test leads are properly connected and not damaged. Verify the correct measurement function is selected.
  • RCD/FI test fails: Check RCD type and nominal current settings. Ensure the RCD itself is functional.
  • Display shows "OVERLOAD" or "OL": The measured value exceeds the instrument's range for the selected function. Disconnect immediately.

If problems persist, contact Benning customer support or a qualified service technician.

8. Spesifikasies

KenmerkSpesifikasie
VervaardigerBenning
Modelnommer044104
Afmetings (L x B x H)11.5 x 10.3 x 23 cm (4.5 x 4.1 x 9.1 duim)
Gewig1.01 kg (2.23 lbs)
Kragtoevoer6 AA NiMH rechargeable batteries (included)
Isolasieweerstandreeks0.01 MOhm - 1000 MOhm
Isolasietoets Voltages50V, 100V, 250V, 500V, 1000V
Low-Ohm Resistance Range0.01 Ohm - 2000 Ohms (200mA test current)
Loop/Line Impedance Range0.01 Ohm - 10 kOhm
RCD/FI Test TypesAC, A, F (Standard and Delayed 'S')
AC/DC Voltage Reeks1 V - 550 V (True RMS)
Frekwensiereeks0 Hz - 20 000 Hz
VoldoeningDIN VDE 0100-600, IEC 60364-6, DIN VDE 0105-100, EN 50110, IEC
Minimum Bedryfsvoltage50 Volt
Maksimum bedryfsvoltage600 Volt

9. Waarborg en Ondersteuning

Benning provides a 1-year availability for spare parts for the IT 115 Installation Tester. For technical support, service, or warranty claims, please contact your local Benning distributor or visit the official Benning webwebwerf.

Always refer to the official Benning documentation for the most up-to-date warranty terms and support information.