Inleiding

This manual provides essential information for the safe and efficient use of your Philips Lighting ER55LD3WR LED Exit Sign. Please read these instructions carefully before installation and operation, and retain them for future reference. This product is designed for commercial lighting applications, specifically as a lighted exit sign.

Veiligheidsinligting

  • Always disconnect power before installing or servicing the unit.
  • Installasie moet deur 'n gekwalifiseerde elektrisiën uitgevoer word in ooreenstemming met nasionale en plaaslike elektriese kodes.
  • Moenie hierdie produk vir ander doeleindes as die beoogde gebruik gebruik nie.
  • Maak seker dat alle verbindings veilig en behoorlik geïsoleer is.
  • Hou weg van water en oormatige vog.

Pakketinhoud

Verifieer dat alle komponente teenwoordig is voordat u met die installasie begin:

  • Philips Lighting ER55LD3WR LED Exit Sign unit
  • Monteer hardeware (skroewe, ankers)
  • Instructiehandleiding (hierdie dokument)

Opstelling en installasie

The Philips Lighting ER55LD3WR LED Exit Sign is designed for wall mounting. Ensure the mounting surface is suitable to support the weight of the unit.

  1. Berei die installasie area voor: Disconnect power to the circuit where the exit sign will be installed.
  2. Montering:
    • Identify the desired wall mounting location.
    • Use the provided mounting hardware to securely attach the exit sign to the wall. Ensure the unit is level.
  3. Bedrading:
    • Connect the building's 120V AC power supply to the corresponding wires on the exit sign. Refer to the wiring diagram inside the unit's housing for specific connections.
    • Verseker behoorlike aarding.
    • Connect the internal battery (if not pre-connected). This is crucial for emergency operation.
  4. Finale Vergadering: Secure any covers or diffusers.
Philips Lighting ER55LD3WR LED Exit Sign, front view

Figuur 1: Voorkant view of the Philips Lighting ER55LD3WR LED Exit Sign. This image shows the white housing with the red "EXIT" lettering illuminated, indicating its primary function as an emergency egress indicator.

Bedryfsinstruksies

Once installed and power is restored, the Philips Lighting ER55LD3WR LED Exit Sign will operate automatically.

  • Normale werking: When AC power is present, the "EXIT" sign will be illuminated by the internal LEDs. The green indicator light on the unit will be ON, signifying operating status.
  • Noodoperasie: In the event of an AC power failure, the unit will automatically switch to battery backup, illuminating the "EXIT" sign for a specified duration (typically 90 minutes).
  • Toetsknoppie: A test button is provided on the unit to verify emergency operation. Press and hold the "Push to Test" button to simulate an AC power failure. The sign should remain illuminated, and the green indicator light will blink, indicating testing. Release the button to return to normal operation.
Philips Lighting ER55LD3WR LED Exit Sign, test button and indicator lights

Figuur 2: Close-up view of the test button and indicator lights on the Philips Lighting ER55LD3WR LED Exit Sign. The green indicator shows operating status (ON for ready, Blinking for testing). The red indicator shows service alerts such as battery, charger board, transformer, or LED strip faults.

Onderhoud

Regular maintenance ensures the reliability and longevity of your LED Exit Sign.

  • Maandelikse Toets: Press the "Push to Test" button for at least 30 seconds to ensure the battery backup system is functioning. The sign should remain illuminated.
  • Annual Test: Disconnect AC power to the unit for 90 minutes to verify the battery can sustain emergency illumination for the required duration.
  • Skoonmaak: Maak die buitekant van die eenheid skoon met 'n sagte, damp lap. Moenie skuur skoonmaakmiddels of oplosmiddels gebruik nie.
  • Battery vervanging: The internal battery has a limited lifespan. If the unit fails to hold a charge or the red "Battery fault" indicator illuminates, the battery may need replacement. Contact qualified service personnel for battery replacement.

Probleemoplossing

Verwys na die volgende tabel vir algemene probleme en hul oplossings.

ProbleemMoontlike oorsaakOplossing
Sign does not illuminate (AC power present)No AC power; faulty wiring; LED strip faultCheck circuit breaker; verify wiring connections; contact service for LED replacement.
Sign does not illuminate during power outage (emergency mode)Battery not connected; discharged battery; faulty battery; charger board faultEnsure battery is connected; allow 24 hours for initial charge; replace battery; contact service for charger board repair.
Red Service Alert indicator is ONIndicates battery, charger board, transformer, or LED strip fault (refer to unit label)Identify specific fault from unit label; perform monthly/annual tests; contact qualified service personnel.
Green Operating Status indicator is OFF (AC power present)No AC power; internal faultCheck AC power supply; contact qualified service personnel.

Spesifikasies

KenmerkDetail
ModelnommerER55LD3WR
HandelsmerkPhilips beligting
LigbrontipeLED
Voltage120 Volt
KragbronElektries met koord
Montage tipeMuurmontering
MateriaalMetaal
KleurWit
Produk afmetings4.25 x 6.25 x 4.8 duim
Item gewig4.98 pond
UPC781370410117

Waarborg en Ondersteuning

For warranty information or technical support, please contact Philips Lighting customer service. Keep your purchase receipt as proof of purchase.

Vervaardiger: Philips beligting

Webwebwerf: Besoek die PHILIPS Winkel op Amazon

© 2023 Philips Lighting. Alle regte voorbehou.